Equation validity
Slump ≤ 175 mm, internal vibration ≤ 1.2 m deep, rate ≤ 2.1 m/h, height ≤ 4.2 m. These are the ACI 347R-14 validity bounds, not IS 14687's. Outside them the tool falls back to full hydrostatic: the conservative design case.
Lateral pressure of fresh concrete on wall and column formwork: ACI 347R-14 SI equation p = Cw.Cc.(7.2 + 785R/(T+17.8)) kPa with the 30 kPa floor
Maximum lateral pressure of fresh concrete on vertical formwork: the ACI 347R-14 equation with its 30 kPa floor and full-hydrostatic cap. Enter wall height, placement rate and concrete temperature.
Cw = Cc = 1.0 for plain OPC normal-weight concrete with normal set.
Equation validity
Slump ≤ 175 mm, internal vibration ≤ 1.2 m deep, rate ≤ 2.1 m/h, height ≤ 4.2 m. These are the ACI 347R-14 validity bounds, not IS 14687's. Outside them the tool falls back to full hydrostatic: the conservative design case.
Design lateral pressure
kPa
ACI 347R-14 Eq. 2.2 (SI): pmax = Cw·Cc·[7.2 + 785R/(T + 17.8)] kPa, where R is the rate of placement in m/h and T the concrete temperature in °C. Fresh concrete stiffens as it gains height: faster pours and colder concrete keep it fluid longer and raise the pressure. The result is floored at 30·Cw kPa and capped at the full hydrostatic head. Pressure physically cannot exceed the weight of the fluid column above.
The equation is valid for internally vibrated concrete with slump ≤ 175 mm, vibration depth ≤ 1.2 m, R ≤ 2.1 m/h and height ≤ 4.2 m. This is an ACI guide equation, not an IS provision, and the bounds quoted here are ACI's own. IS 14687:1999 has a method of its own for this step: Cl 7.3.2.4 gives curves of typical lateral pressure per unit height on formwork in Fig. 3, with Table 1 correction factors for degree of workability at rates of placement up to 1, 1.5–2 and 2.5–4 m/h. The calculator runs the ACI equation because it is closed-form and states its validity range; CIRIA R108 is the common alternative for tall walls with blended cements.
Given: retaining wall 3.0 m high, poured at 2.0 m/h, concrete at 25°C, normal OPC.
p = 1.0 × 1.0 × [7.2 + 785×2.0/(25 + 17.8)] = 7.2 + 36.7 = 43.9 kPa
Floor 30 kPa < 43.9; hydrostatic cap 24×3 = 72 kPa > 43.9 → design at 43.9 kPa, equivalent fluid head 43.9/24 = 1.83 m. The bottom panels and ties near the 1.8 m zone see the full design pressure.
IS 14687:1999 gives the framework, loads, materials, tolerances and safety, and a lateral-pressure method of its own. Cl 7.3.2.4 gives curves of typical pressure per unit height on formwork in Fig. 3, read with Table 1, the correction factors for degree of workability (very low, low, medium, high) at rates of placement up to 1, 1.5–2 and 2.5–4 m/h. This tool runs the closed-form ACI 347R-14 equation instead, and the validity limits it applies, slump ≤ 175 mm, rate ≤ 2.1 m/h, height ≤ 4.2 m, are ACI's, not IS 14687's. CIRIA R108 is the other routine basis for the pressure side of formwork design worldwide.
Whenever the stiffening assumptions fail: slump above 175 mm, retarders or slow-setting mixes, self-compacting concrete, vibration deeper than about 1.2 m, placement rates above 2.1 m/h, or walls taller than 4.2 m. Pressure can never exceed the fluid head γ·h. Hydrostatic is the physical ceiling and the safe default.
Cw adjusts for concrete unit weight (1.0 for normal-weight concrete around 23.5 kN/m³); Cc adjusts for chemistry. Cement blends, retarders and cold slows of set raise it. Both are 1.0 for plain OPC normal-weight concrete with normal set.
No. The equation gives the maximum pressure, which occurs near the base of the placement. Formwork is designed for an envelope: full design pressure over the lower zone tapering towards the surface. The effective head shown here, design pressure divided by unit weight, is the equivalent fluid column depth.
Often used together with this calculator. Pick the next step in your design or QA loop.
This is the same calculator ConcreteInfo publishes on the main site. It runs in your browser, with no account and nothing to install.